Hi!
We ran UPS tests last night and it came out that our UPS configuration isnt working at all.
We have couple of Esxi5.5 nodes with vcenter and HA, couple of physical servers, 2 Eaton 5PX 3000 UPSs. IPM 1.42 is installed on physical windows machine. When we disconnected UPSs from power grid their status on IPM went to error, as it should be. However the Virtual Power Source stayed green and propably because of that IPM never sent shutdown commands to any of the hosts.Also the UPSs battery runtime and capacity didnt update after ~80% / 12min, which lead us to believe it was safe to plug in the UPSs again. It wasnt. The shutdown sequence had already begun and in a minute we were left without power crashing all our hosts, Network anddisk storage systems.
Soo, couple of questions before trying this again.
Obiously the VPS was miscongured. It...